Gaurika Trading Company Hydrant valves (also called Landing valves) provide the means to draw water for firefighting from the Fire water piping network. They are normally mounted onto dry/wet risers or on stand posts, fitted on the fire water network.
| Model | G108-BS |
| Size & Inlet |
2½” (65 mm)
Inlet: Threaded - G 2½ MBSP Thread (BS EN 10226)
|
| Outlet | 2½” (65 mm) Female Inst. Adaptor |
| Reference Standard | BS:5041 / BS:336 |
| Material |
Body, Bonnet & Female Outlet: Bronze BS:1400 LG2
Spindle: Brass BS:2874
Spring: Phosphor Bronze Wire
Hand Wheel: Cast Iron, BS:1452
Washer: Rubber, BS:1154
|
| Test Pressure |
Hydrostatic Test (Body): 22.5 Bar (2 min)
Water Tightness (Seat): 16.5 Bar (2 min)
|
| Performance | Flow Test: 510 +/- 30 lpm at 4.7 Bar |
| Working Pressure | Up to 15 Bar |
| Weight | Approx. 5.0 Kgs |
| Finish | Body: Fire Red Color | Hand Wheel: Black Paint | Parts: Polished |
| Warranty | 12 Months from the date of supply |